TA2-HL

DO NOT USE INSIDE COOLER OR FREEZER!

No power is required

TA-2HL has been designed for reliable monitoring of non-condensing (indoor only) environment areas where high and low temperature limits are critical. This unit will separately zone out high and low temperature alarm signals. This unique feature enables you to instantly identify whether your facility being monitored has a high or low temperature condition.

Power Requirement  No power required to operate.
Operating Temperature Alarm Use 50 to 130° F (10 to 54° C); non-condensing environments only.
Alarm contacts may not function as accurately outside of this range
Display Use -30 to 130° F (-34 to 54° C); non-condensing environments only.
Low Limit Adjust Range -30 to +120° F (-34 to +49° C)
High Limit Adjust Range -20 to +130° F (-29 to +54° C)
Temp Accuracy ±3° F (±1.7° C)
Temp Response Time TC 14 minutes
Temp Sensing Element Bimetallic Coil
Outputs Gold plated N.O. dry contacts (Not for high voltage use.)
Contact Output Rating 50mA @12VDC
Weight 12 oz (340 g) 
 Operating Temperature Alarm Use: 50 to 100° F (10 to 38° C) is because the TEMP ALERT is most accurate within that range.   

Manual